CN (Connect Next)
For salvo switching on alarm contact receipt:
1. Position the cursor to the CN column and desired ACN.
2. Press the ENTER key to cycle through the CN
selections. Press the NEXT key to accept the displayed
selection.
or
Enter a number for one of the following selections and
press the ENTER key. (The second number of each
selection adds the “*” feature to the CN selection, e.g., 8
= W*.)
1, 5 = N, no connect next
2, 6 = Y, connect the next entry in a salvo
3, 7 = S, call a System Salvo
4, 8 = W, activate all contiguous ACN entries
If No (N) is selected, the CAM number for this ACN entry is
called on receipt of the alarm contact.
If Connect Next (Y) is selected, a camera salvo group is
defined for callup by the first ACN of the group. All
contiguous entries in a salvo group must be set to Y, except the
last entry which is set to N or S. The dwell time for all entries
of the salvo group is determined by the first entry of the group;
the dwell time for all other entries in the salvo group may be
left blank.
If System Salvo (S) is selected, the CAM number for this ACN
entry must be set to the desired System Salvo number. This
System Salvo is called on receipt of the alarm contact.
If Wired (W) is selected, all contiguous ACN entries in the
Wired set are activated when any alarm contact of the set is
received. Each ACN in the set is then handled as a separate,
active alarm for the monitor it is armed to.
• All contiguous ACN entries in a Wired set must be set to
W, except the last entry which is set to N or S. The last
entry (N or S) is also activated as part of the Wired set.
More than one Wired set may be specified in the ACN list;
an alarm contact received in one Wired set does not activate
any other alarm contacts in other Wired sets.
• The “*” symbol is used in Wired set ACN entries only.
When an ACN with a “*” is manually Acknowledged, all
alarm contacts in that Wired set are cleared. A manual
Acknowledge for any ACN which does not include the “*”
clears that ACN only. Any or all ACN entries in a Wired
set may include this symbol in the CN field.
Note: If Pseudo numbers are used, the CAM number switches
between Pseudo numbers when N, Y, or W is selected and
Real numbers when S is selected.
Example: Define ACN 0001 as the start of a 3-camera salvo,
and ACNs 0006 - 0008 as a Wired set. A Manual Clear of
ACN 0007 clears all three ACNs in this set.
ALARM CONTACT SETUP
ACN CAM DWL PRE AUX CN
0001 0001 02 00 0 - Y
0002 0002 00 00 0 - Y
0003 0003 00 00 0 - N
0004 0004 02 00 0 - N
0005 0005 02 00 0 - N
0006 0006 02 00 0 - W
0007 0017 30 05 1 ON W*
0008 0008 02 00 0 - N
.
.
0016 0016 02 00 0 - N
PREVIOUS MENU
ALARM RESPONSE ACTION
When an alarm contact activation is received, the camera video
associated with that alarm contact is displayed on the monitor
that is armed and associated to that contact.
In order to provide this automatic video callup, the required
cameras and monitors must be programmed and armed for
alarm response. This includes associating alarm contacts to
cameras and monitors, and arming each monitor, as follows.
1. Associate Alarm Contacts with Cameras - use the Set
Alarm Contacts menu, above.
2. Associate Alarm Contacts with Monitors - use the
Monitor/Contact Access menu, page 4-29.
3. Arm the Monitors - use the Monitor menu, page 4-18.
Refer to the Appendix, pages A-3 to A-7, for further
description of Alarm Programming.
4-15
AD1024 MENU PROGRAMMING