The School Board of Miami-Dade County, Florida
Bid No. 113-CC04
Surveillance Camera Systems, Closed Circuit, (Furnish and Install)
Specifications
4.23 The cost or credit to the School Board of Miami-Dade County, Florida resulting from a change in the work shall
be determined in one of the following ways:
a. By mutual acceptance of a properly itemized lump sum amount supported by sufficient substantiating
data to permit evaluation, if not listed in the Contract Documents.
b. By unit prices stated in the Contract Documents or as subsequently agreed to.
4.3
FAMILIARITY WITH LAWS
The vendors are presumed to be familiar with all Federal, State and Local Laws, Ordinances, Code Rules and
Regulations that may affect the work in any way. Ignorance on the part of the vendor(s) shall in no way relieve
the vendor from responsibility. Vendors are advised that The School Board of Miami-Dade County and the
Florida Department of Education may have additional requirements beyond those contained in the locally
accepted Building Codes.
4.4
DEFINITIONS
4.41 Cabling shall be considered to mean: data, low voltage Class II power and video transmission cabling, and shall
include all copper wires, copper multi conductor cables, fiber optic strands and multi strand fiber optic cable.
The words wire and cable are intended to have the same meaning and are used interchangeably.
4.42 Conduits: Shall be construed to include all metal and plastic tubing, all cable trays and ducts in which SCS-
CCTV camera and/or low voltage Class II cabling may be installed. These items are also referred to as
raceways.
4.5
CONDUIT DESIGN
4.51 The basic design for SCS-CCTV for new and existing school and non-school site buildings shall be as follows:
a) a central control room shall be identified by the MO/OSP Project Manager in conjunction with the site
administrator
b) there may be satellite cable termination rooms and/or closets in each building as determined by the
camera layout
c) the locations of the satellite cable terminal rooms and/or closets shall be such that the maximum lineal
cable distance from a cable terminal room or closet to an associated camera is 300 feet
d) the SCS-CCTV equipment rack shall be located in the central control room
e) supply and install camera infrastructure raceways as required. All raceway strapping shall be in
accordance with National Electrical Code and M-DCPS Specs
f) not all cabling installations require conduit
g) all cabling shall be supported as prescribed by M-DCP Master Specifications
h) raceways will be determined by the camera layout. MO/OSP shall review for adequacy, the actual
quantities and sizes of the conduit during the design phases of the project
i) there shall be a minimum of one conduit of a minimum of a 2" diameter from the control room to each
satellite room and closet
j) exposed raceway shall be painted to match existing structure, junction box covers shall be painted in
L Leasburg-Kramer
11 3/16/2004