The School Board of Miami-Dade County, Florida
Bid No. 113-CC04
Surveillance Camera Systems, Closed Circuit, (Furnish and Install)
Specifications
gold color; underground raceway shall be painted to meet Master Specification requirements
4.52 Design for laying out conduit systems for the central control room and the various satellite cable termination
rooms and closets shall be based on the following requirements:
4.53 Every satellite cable termination room may have:
a) voice jack and data jacks that shall be connected to a satellite room or closet using 4-pair category 5e
cable. It is intended that five of the seven data jacks be used for 100 MB data. Fiber optic cable shall
be used between the main equipment room and satellite rooms and closets for 100 MB data. Multipair
copper cable shall be used between the main telephone room and satellite rooms and closets for the
jack and one data jack.
b) there shall be no daisy chaining of outlet boxes except where approved by the MO/OSP Project
Manager.
4.54 Wire termination at the various cable termination rooms and/or closets shall be as follows:
a) all SCS-CCTV junction boxes/punch-down blocks must be labeled “SCS-CCTV” and shall be painted in
gold coloring
b) all SCS-CCTV punch-down blocks located in the central control room shall be installed on a designated
CCTV punch-down board
c) all SCS-CCTV cable punch-down blocks located within cable termination closets shall be enclosed
inside junction boxes
d) location of all punch-down blocks will be determined by the MO/OSP Project Manager
e) all SCS-CCTV power supplies shall be wired with flexible A/C outlet cords not to exceed twelve (12)
inches in length. Exceptions to the twelve (12) inch cord length must be approved in writing by the
MO/OSP Project Manager
f) fiber optic cable shall be terminated in a suitable interface unit that provides for fan-out of the strands
and termination in ST-type connectors. The number of strands and arrangement of separation and fan-
out shall be approved by MO/OSP.
g) all SCS-CCTV cable terminations shall be labeled and punched-down neatly into the following distinctly
identifiable groups:
1) Security
2) Video
3) Data
4.55 Installation and configuration of video transmission devices, hubs, switches and network management stations:
a) vendors shall be required to install as directed by the MO/OSP Project Manager
4.56 The types of conduit and the locations where each type may be used shall be governed by the Miami-Dade
County Public Schools Master Specifications. This document can be found at
http://facil.dade.k12.fl.us/facplan/Masterspec.htm
4.6
INSTALLATION PRACTICES
a) All SCS-CCTV cabling and terminations shall be installed according to the best industry practices and
manufacturer's specifications. Cable not in conduit shall be plenum rated and meet fire code
requirements. All cable shall be neatly run and have proper mechanical protection. Cables shall be
L Leasburg-Kramer